Explosion-proof split ultrasonic level gauge

Sincerely thank you for choosing our ultrasonic level gauge!This instrument contains a number of self-developed patented technologies and has a new signal processing technology. It has the characteris

National Service Hotline:

13116702695

Sincerely thank you for choosing our ultrasonic level gauge!


This instrument contains a number of self-developed patented technologies and has a new signal processing technology. It has the characteristics of safety, cleanliness, high accuracy, long life, stable and reliable, convenient installation and maintenance, and simple readings. It is widely used in petroleum, chemical, and water treatment. , Water conservancy, iron and steel, coal mine, electric power and food processing industries, applicable to various fields such as acid, alkali, salt, anticorrosion, high temperature, explosion-proof and so on.


This instrument can be connected to various DCS systems through 4 ~ 20mA or RS485 (Modbus protocol) to provide real-time liquid level data for industrial automation operation.


The explosion-proof ultrasonic level gauge has the following characteristics:


Safety


It adopts die-cast aluminum alloy waterproof and explosion-proof housing.


2. Stable and reliable


In the circuit design, we select high-quality modules and key components from the power supply section to choose highly stable and reliable components, which can completely replace the imported instruments.


3. Patented technology


Patented sonic intelligent technology software can perform intelligent echo analysis without any need


How to debug and other special steps, this technology has the functions of dynamic thinking and dynamic analysis.


4.High accuracy


The sonic intelligent patent technology owned by our company has greatly improved the accuracy of explosion-proof ultrasonic level gauges, and the level accuracy has reached 0.3%, which can resist various interference waves.


5.Low failure rate, easy installation and easy maintenance


This instrument is a non-contact meter, and does not directly contact the liquid, so the failure rate is low. The meter provides a variety of installation methods. Users can completely calibrate the meter through this manual.


6. Multiple protections


The protection level of the instrument reaches IP65; all input and output lines are protected against lightning and short circuits.


This information is for reference only. In order to continuously improve product performance, all pictures and performance parameters on this website are subject to change without notice, please forgive me! The company reserves the right of final interpretation of all technical parameters and pictures.

  1. Technical indicators and selection codes

    图片关键词

2.Parameter setting


2.1 Instrument calibration steps


1) The meter is powered on, the meter enters the measurement, and the LCD displays


Display the liquid level value, as shown on the right, and the measured liquid level


Picture keywords


It is 3.320m, the calibration method is introduced below.


2) Click the Mode button, the meter


You can enter the parameter setting menu, first enter


The P01 (Level) level calibration menu.


3) Click the OK button to enter the level calibration input


Interface, input the measured liquid level value 3.320m,

As shown on the right, press the Mode button to return after setting


Level menu.


4) Click the Mode button again as shown on the right.


Mode key to return to the parameter setting menu, click OK


Press to exit the parameter setting menu.


5) The meter displays the measured liquid level, after which the meter reads


The number will correctly reflect the actual liquid level on site.


2.2 Parameter 4 ~ 20mA setting


1) When the meter works normally, click the Mode button to enter the parameters


After setting the menu, press the ▼ key to select the P02 (4-20mA) setting menu, as shown on the right.


2) 20mA setting


a) Click the OK button to enter the 20mA parameter setting


Set the menu, the LCD display is as shown on the right.


b) Click OK to enter the 20mA value input


Enter the interface, enter the value, as shown on the right, table


Output 20mA when the liquid level reaches 5m, set the picture keywords


Then press the Mode key to exit.


3) 4mA setting


In the 20mA parameter setting menu point ▼ key to enter


Enter the 4mA parameter setting menu, click OK


Enter the setting, the method is the same as above.


2.3 Relay parameter setting


1) When the meter works normally, press the Mode key to enter


After entering the parameter setting menu, click the ▼ key to select to


P03 (Relay) relay setting menu, such as


Shown on the right.


2) Click OK to enter the relay 1 setting


    Menu as shown on the right.


3) Click ▼ to select other relays.


OK key to enter the relay 1 setting interface, such as


Right, the formula in the interface represents relay 1.


Closed when the liquid level is greater than 4m and less than 8m. Thesymbol positions in the interface can be selected as "<"> two types of symbols, and the position of the & symbol can be selected as "&", "|", "N" and "change". The symbol to be modified flashes. Press the ▲ key or the ▼ key to select the desired symbol. The numbers are modified as before.

Meaning of symbols:


<: Less than sign


>: Greater than sign


&: And, means that both conditions need to be met;


|: Or, it means that one of the two conditions is met;


N: Only the previous condition, the latter is not displayed;


∧: The former condition is the relay pull-in condition (usually used to open the pump), and the latter condition is the relay


Open condition (usually used to stop the pump), mainly used for drainage well and inlet well control.


4) If the relay is set as shown on the right, it means the relay


The device is closed when the liquid level is less than 1m. If "<"


The symbol changes to a ">" symbol, which means that


The appliance closes when the liquid level is greater than 1m.


If the relay is set as shown on the right, the relay is closed when the liquid level is less than 1m or greater than 9m.


5) There is also a more complex logic, such as drainage


Well, when the water level rises to 8m, the pump needs to be opened for drainage,


Stop the pump when the water is discharged to 2m, this logic setting


As follows:> 08.00∧<02.00, as shown on the right.


At this time, it means that the water level is greater than 8m


Stop the pump when the position is less than 2m.


In the case of inlet wells, for example when the water level drops

图片关键词

At 1m, the pump needs to be turned on to enter the water. When the water level reaches 6m


Stop the pump. This logic is set as follows:


<01.00∧>06.00, as shown on the right.

6) After setting the parameters of relay 1


Mode key returns to Relay relay setting


Setting menu, click ▼ button to select the desired setting


Other relays: for example,


Indicates that relay 2 is set. Click OK


Enter the setting, the method is the same as above.


2.4 Transducer height setting


The P04 (TH) menu does not need to be set when the liquid level has been set using the Level menu. You can refer to the transducer height at this time.


2.5 Display mode setting


P05 (Xstyle) menu can set the display mode, where


1. The Level option displays the liquid level and relay status on the LCD.


2. The AirH option displays the spatial distance and temperature on the LCD.


3. The LevelT option displays the liquid level and temperature on the LCD.


Click OK to select.


2.6 Window menu


The P06 (Window) menu is set at the factory and generally does not need to be changed.


2.7 Address ID number setting


P07 (ID) menu is used for communication, especially for multi-machine communication, the default is 01.


2.8 Baud rate setting


For P08 (BUAD) menu communication, there are three options of 2400, 4800 and 9600. Click OK to confirm. The default is 4800.


2.9 PWDB settings


The P09 (PWDB) menu is set at the factory and generally does not need to be changed.


2.10 4 ~ 20mA setting output


P10 (T4 ~ 20mA) menu point, the displayed value is the output current value after entering the OK button.


Use the ▲ key or the ▼ key to select different current outputs, which can be used for field verification or mutual correction with the control room current input equipment.

 


This information is for reference only. In order to continuously improve product performance, all pictures and performance parameters on this website are subject to change without notice, please forgive me! The company reserves the right of final interpretation of all technical parameters and pictures.

This information is for reference only. In order to continuously improve product performance, all pictures and performance parameters on this website are subject to change without notice, please forgive me! The company reserves the right of final interpretation of all technical parameters and pictures.