LD-5300 series artificial intelligence thermostat / regulator

Overview:LD-5300 series artificial intelligence thermostat / regulator uses real artificial intelligence formula. The meter starts the self-tuning function. It can automatically find the optimal param

National Service Hotline:

13116702695


图片关键词

Overview:

LD-5300 series artificial intelligence thermostat / regulator uses real artificial intelligence formula. The meter starts the self-tuning function. It can automatically find the optimal parameters according to the characteristics of the controlled object to achieve a good control effect. No manual tuning parameters . The accuracy of temperature control is basically ± 0.1 ℃, without overshoot and undershoot, reaching the international advanced level. It can be used with various sensors and transmitters to realize the measurement and display of temperature, pressure, liquid level, capacity, force and other physical quantities, and cooperate with various actuators to perform PID adjustment and control of electric heating equipment and electromagnetic and electric valves , Alarm control, data acquisition and other functions, suitable for industrial furnaces, electric furnaces, ovens, test equipment, shoemaking machinery, injection molding machinery, packaging machinery, food machinery, printing machinery and other industries.

★ Dual-screen LED digital display with light beam analog indication function (0 ~ 100%).

★ With 36 kinds of signal input functions, the input signal type can be selected arbitrarily; 0.2% level measurement accuracy.

★ With alarm functions such as "upper and lower limit alarms", "deviation alarms", "LBA alarms", "flashing alarms", with LED alarm light indication.

★ It can take one PID control output and one analog variable output, with current, voltage, SSR drive, single / three-phase thyristor zero-cross trigger, relay contact and other output control options.

★ With heating (cooling) one-way control and heating and cooling two-way control optional.

★ With PID parameter auto-tuning function, control output manual / automatic disturbance-free switching function, accurate control and no overshoot.

★ Support RS485, RS232 serial interface, using standard MODBUS RTU communication protocol.

★ The meter can be equipped with RS232C printing function, with manual printing, timing printing, alarm printing and other functions.

★ With DC24V feed output, power distribution for field transmitter.

★ The input, output, power, and communication adopt photoelectric isolation technology.

★ With a variety of external sizes and styles for users to choose.

★ Parameter setting password is locked, parameter setting is saved permanently after power off, and it has the function of parameter recovery system original setting.



Instrument wiring diagram



Wiring diagram of ld-5310 single input PID temperature controller / regulator


图片关键词

The specifications and dimensions are a, B, C, D, e, K, l, M type wiring diagram

Note: the wiring terminal directions of the back cover of horizontal and vertical instruments are different, see diagram 1.

图片关键词

The specification and size are F-type wiring diagram

 

图片关键词

The specification and size are H-type wiring diagram

Note: if different functions are marked on the same group of terminals in the above wiring diagram, only one of them can be selected. For example, RS485 and RS232 are on the same group of terminal blocks, only one can be selected.

Ld-5320 dual input (external setting) PID thermostat / regulator wiring diagram

图片关键词

The specifications and dimensions are a, B, C, D, e, K, l, M type wiring diagram

Note: the wiring terminal directions of the back cover of horizontal and vertical instruments are different, see diagram 1.

图片关键词

The specification and size are F-type wiring diagram

Note: if different functions are marked on the same group of terminals in the above wiring diagram, only one of them can be selected. For example, RS485 and RS232 are on the same group of terminal blocks, only one can be selected.

Ld-5330 dual input (valve position control) PID thermostat / regulator wiring diagram

             图片关键词

The specifications and dimensions are a, B, C, D, e, K, l, M type wiring diagram

Note: the wiring terminal directions of the back cover of horizontal and vertical instruments are different, see diagram 1.

图片关键词

The specification and size are F-type wiring diagram

Note: if different functions are marked on the same group of terminals in the above wiring diagram, only one of them can be selected. For example, RS485 and RS232 are on the same group of terminal blocks, only one can be selected.


This information is for reference only. In order to continuously improve product performance, all pictures and performance parameters on this website are subject to change without notice, please forgive me! The company reserves the right of final interpretation of all technical parameters and pictures.

Instrument selection


1568085975372582 (2).jpg


Remarks:


1. Auxiliary output can be used as transmission output or control output, which can be selected in the secondary parameter “HC”. When HC = 0, it is transmission output, and when HC = 1, it is control output; the main control output and auxiliary The output cannot select the three-phase thyristor zero-crossing trigger pulse output function at the same time; when the LD-5330 valve position control output selects the switch value forward and reverse control output, the auxiliary output can only select analog control; the F-type instrument control output selection switch When the output is positive or negative, the auxiliary output can no longer be provided; the H-type meter cannot select the auxiliary output function.

2. The gauges of size F and H do not have RS232C printing interface; the gauges of size H are only for single-channel control.

3. The size is H and the D and E meters with alarm function between 25-36 terminals. The relay contact capacity is AC125V / 0.5A, DC24V / 0.5A, and the relay contact capacity of other specifications is AC220V. / 2A, DC24V / 2A.

4. When the control output selects digital control output, the alarm output can only select 2 limit alarms at most.

5. When the model LD-5310 / 5320 control output selects K1, it refers to a single relay output.

6. The selection must be complete, and the function items that are not selected cannot be omitted, and must be filled in with "X".

Example 1: LD-5310A-14 / X-0 / 0/2 / X / X-A (single control)

Example 2: LD-5320A-14 / 27-K1 / 0/2 / D1 / X-A (outside given control)

Example 3: LD-5330A-14 / 27-0 / 0/2 / Y1 / X-A (valve position feedback control)

Example 4: LD-5330A-14 / 27-K1 / 0/2 / D1 / XA (valve position feedback input forward and reverse control output) Example 5: LD-5330A-14 / X-K1 / X / 2 / X / XA (forward and reverse control output without valve position feedback input)


This information is for reference only. In order to continuously improve product performance, all pictures and performance parameters on this website are subject to change without notice, please forgive me! The company reserves the right of final interpretation of all technical parameters and pictures.

This information is for reference only. In order to continuously improve product performance, all pictures and performance parameters on this website are subject to change without notice, please forgive me! The company reserves the right of final interpretation of all technical parameters and pictures.